If the lights are on two channels on the same controller, the channels can be bridged. If they are on two different controllers, data points are transmitted over IP using OPC XML-DA, BACnet client or global connections. The figures apply to the LDALI-ME201-U, ME202-U and ME204-U models.
Two channels on the same controller: DALI channel bridging
Two or more physical channels are linked into one virtual channel. Group commands and broadcasts received on one channel are forwarded to the bridged channels. A command to group 1 reaches group 1 on all bridged channels. Bridging has no effect on commands to a short address, so a command to device 1 on channel 1 does not reach device 1 on channel 2 (LTRAIN-DALI). Bridging is used when a group needs more than the 64 ballasts that fit on one channel, and requires a controller with more than one channel (ME202-U, ME204-U).
LOYTEC states that bridging is only necessary if the large group is also controlled by other DALI masters, e.g. DALI push-buttons or panels. Otherwise the manual recommends local or global connections to link groups across channels (on the LON models also fan-out bindings).
Two controllers: what is connected
| Task | How it is done |
|---|---|
| A push-button on controller A controls a group on controller B | The status of the push-button is made into a binary data point that is passed to B. The data point is first selected as a trigger in the L-INX Configurator. It can then be selected on the Buttons page in B’s web interface, with the group as the Destination. |
| The sensor on A is used by the constant light controller (CLC) on B | On the CLC Bindings page, ”Choose data point…” is selected as the input. An analogue data point can be used as a lux sensor, a binary one as presence. A CLC has one lux input and up to 16 presence inputs. |
| A controls a group on B directly | On LDALI-ME20x, a group is controlled via a BACnet Analog Output object, to which the other controller can write. Read about the priorities, before you write to the group, because the value stays there until it is released. |
The Neighboring Controllers function keeps neighbouring zones at a low level when a zone is in use, with up to 16 neighbours per CLC. The manual describes it for zones in the same open-plan office, but does not say whether the neighbours can be on a different controller.
How the data points are passed between the controllers
OPC XML-DA client
According to ARINN's experience, this is the easiest way in practice.
- Set the OPC flag on the data points to be shared on controller A (the OPC column in the L-INX Configurator).
- Right-click on the folder and select Export OPC Tags… The file ends with .opc.
- On controller B: right-click on the OPC Client folder and select New OPC Device… Select the .opc file.
- Select Commission later. The IP address of A is then entered afterwards in B’s web interface. If a subtree is imported, its base path can also be changed on the same page, e.g. if two subtrees are identical.
- Download the configuration to both controllers.
You can also choose A’s project file (.dali) instead of an .opc file. OPC XML-DA is a web service on http://<controller A>/DA over the web server port, 80 by default, with basic authentication as operator. If the controllers are on separate networks, the port must be open between them. The LDALI-ME20x has 10,000 OPC data points.
BACnet client
Controller B creates a BACnet client mapping against objects on controller A, e.g. the Analog Output object that controls the group. Access is set to Poll, COV, COV unsol or Auto, where Auto chooses the best method itself. The LDALI-ME20x has 1,000 BACnet client mappings.
Global connections
The function is disabled from the factory and is enabled with the Global Connections (CEA-852) checkbox on the Ethernet tab in the port configuration. The controllers must be in the same IP-852 channel, which is defined by adding them to a configuration server. The channel only delimits which devices exchange data and has nothing to do with the CEA-709 technology.
The connection is created under the Global Connections tab in the L-INX Configurator. Data is matched on the connection name. The definitions can be exported and imported on the other controller. Global connections cannot use adapters. If a value needs to be converted, a register data point with a local connection is used. The LDALI-ME20x has 250 global connections.
Delay
Our search in the manuals does not find a figure for the delay over global connections or OPC. Two things can be set for a global connection: Min Send Time delays the next transmission and limits the send rate, and Max Send Time sends the value again even if it has not changed. If two controllers must react simultaneously, measure it on the installation.
What the manuals do not cover
Our search finds no ready-made recipe for two LDALI-ME204-U controllers regulating luminaires in one room as one group with shared constant light control. The above are the building blocks LOYTEC describes. If you are faced with that case, then contact ARINN.
Sources: LOYTEC Device User Manual 8.6 (sections 6.1.1, Global Connections Configuration and 16.3.10), L-DALI User Manual 8.6 (sections 8.2.4.9, 8.4.1 and 8.4.3), LINX Configurator User Manual 8.6 (sections 3.3.4, 3.7.1, 4.5.7 and chapter 13), LTRAIN-DALI v4.0, datasheet LDALI-ME20x-U. The OPC client route has been tested by ARINN on its own devices. In the event of a discrepancy, the datasheet and manual apply. Last reviewed 5 November 2026.