The constant light controller (CLC) on an LDALI-ME20x writes the group at its own BACnet priority, 16 by default. It can be set per CLC under CLC Bindings. If a value sits at a higher priority (lower number), it wins. The CLC is still in automatic mode with Auto_Mode = active, and its output shows the value it wants.
Tested by ARINN on an LDALI-ME204-U, firmware 8.4.18, October 2026: the group had priority 8 = 0 from a test write by a script 17 days earlier and priority 16 = 100 from the CLC. The CLC wanted to switch on (185 lx against a setpoint of 500 lx) and was in automatic mode while the light was off.
How to see it
In the web interface: Data → Data Points → BACnet Port → Datapoints → the channel → Group Actuators → the group → click the data point Group. The detail page shows the whole priority list under Native Info:
[1..16|Dflt] = {-,-,-,-,-,-,-,0,-,-,-,-,-,-,-,100|0}
Here slot 8 = 0, slot 16 = 100 and Relinquish_Default = 0. Edit Priority Array on the same data point shows the same and can clear a slot.
Two kinds of override
| The CLC’s own override | BACnet value for the group | |
|---|---|---|
| Characteristics | Auto_Mode inactive, e.g. after a DALI push-button press | Auto_Mode active, but a value sits at a higher priority than the CLC’s |
| Comes from | A push-button, or a write to the CLC’s Override | A script, the web interface or a head-end writing to the group |
| Released with | Override = -1 or invalid, the scene AUTOMATIC MODE (state 49), the button function Auto with the group as destination, or an empty room in the operating modes with automatic release | The slot is cleared with clear in Edit Priority Array, or whoever wrote it writes NULL at the same priority |
On the tested device, neither the scene AUTOMATIC MODE nor Override = -1 touched a value at priority 8 in the group’s priority list.
When the slot is cleared
The group falls to the next occupied slot. On the tested device that was the CLC’s 16, and the light followed the CLC again. If nothing sits below, the object falls to Relinquish_Default, and on the tested device that was 0 %, so the light switched off. The property can be written and may be different in an installation. Look through the list first, and only clear slots where you know who wrote them.
If lamp or channel values are cleared on a channel in operation, all lamps not held by a CLC or another priority switch off, including lamps another party has set.
After an override on a lamp or channel
On the tested device, clearing priority 8 on a single lamp or on the channel did not give light when nothing sat below it. The CLC did not resend its value by itself. The lamps in the CLC’s group were still off after 8 seconds, while the CLC’s output was at 100 %.
The following is what a script did on the test unit. This is not an approach for an installation in operation:
- NULL on the lamps, the channel and the groups that had been written to.
- The CLC’s Override setting is set to -1 or NULL.
- After less than a second, a nudge on each group above 0 %: a value 1 % off the CLC’s, written at a priority above the CLC’s, then NULL.
The first time it had to be repeated before everything was back. The cause has not been found. The nudge itself writes at a higher priority and must be released with NULL again, otherwise the problem is still there. Lamps outside a CLC group switched off because they fell to the default value.
Override = -1 stays as a value, and the web interface then shows ”Override active: -1%!” under CLC Bindings, even though the CLC is in automatic mode. NULL on Override also gives automatic mode, and the line is not shown (tested from a script on an LDALI-ME204-U, firmware 8.4.20, November 2026). If the scene AUTOMATIC MODE is written from a script, the number 49 stays at the script’s priority in the scene object’s own list (tested). Release it with NULL.
Where a left-over value can come from
- A JavaScript script on the controller: on the tested device, the writes landed at priority 8.
- A manual write from the web interface: we have not measured which priority it lands on. Check in Native Info.
- A head-end writes at the priority it is configured with.
What they have in common is that the value stays until whoever wrote it releases it with NULL, or the slot is cleared.
Operating modes that release the CLC’s own override by themselves
REGULATOR_AUTO, CONTROL_AUTO and PRESENCE_AUTO release the CLC’s own override when the room becomes empty. The BEDROOM operating modes only do so if the light is on. REGULATOR, CONTROL and the others release only manually. It is the CLC’s own override that is released. Whether a left-over value on the group’s priority list also moves, we have not measured, and our search in the manual does not find it. The operating mode must not be changed during operation, and a restart is required after a change.
If two controllers are to share lights, the routes are on the page about two DALI controllers for the same light.
Sources: ARINN’s tests on an LDALI-ME204-U, firmware 8.4.18 and 8.4.20, October and November 2026. L-DALI User Manual 8.6, sections 8.2.2.13 (the scene object), 8.2.4.3 (table 33) and 8.2.4.4. LTRAIN-DALI v4.0 (default priority 16). The path in the web interface and the display of the list were read off the test device. The tests apply to the device and firmware mentioned. Last reviewed 5 November 2026.